To follow up from my previous post... here is a picture of a 48kwh Panda battery. it has three 314ah cells in parallel with no fusing between cells. If one cell were to short out, the other 2 peers would dump amps into it and likely make a lot of heat. This is poor engineering practice. The 32kwh panda is the same it just uses two 314ah cells the same way.
For comparison here's a picture of a yixaing 32kwh battery with individual MB56 cells. Much better, much safer.
Post #11193
266
Off The Grid If you are going to order a 32kwh battery, be aware of three things: 1)It MUST use MB56 cells. Several manufacturers are placing two 314ah cells in parallel to make the capacity. This is NOT good engineering practice. 2)You might calculate that you need…